Voltage profile of the IEEE 118-bus system
Solve the power flow of MATPOWER's case118 (the IEEE 118-bus test system, a
model of part of the American Electric Power system in the Midwestern
United States) with
vp.power.runpf, and plot every bus's voltage magnitude and angle. The
Newton-Raphson solution is compared with the linear DC model, which assumes
flat 1.0 per-unit magnitudes and lossless branches, and with the solution
when generators are held to their reactive limits.
The AC solution
Newton-Raphson in polar coordinates from the case's starting voltages. The 54 generator buses hold their voltage set points; the 64 load buses settle where the reactive power balances.
import numpy as np
import vipyr as vp
from vipyr.figure import figure
nr = vp.power.runpf("case118")
print("converged:", nr.success, "in", nr.iterations, "iterations, largest mismatch %.1e per unit" % nr.mismatch)
print("Vm from %.4f to %.4f per unit" % (nr.vm.min(), nr.vm.max()))
print("Va from %.2f to %.2f degrees" % (nr.va.min(), nr.va.max()))
print("generation %.1f MW for %.1f MW of load: losses %.1f MW" %
(nr.pg.sum(), nr.bus[:, 2].sum(), nr.pg.sum() - nr.bus[:, 2].sum()))converged: True in 3 iterations, largest mismatch 1.5e-12 per unit
Vm from 0.9430 to 1.0500 per unit
Va from 7.05 to 39.75 degrees
generation 4374.9 MW for 4242.0 MW of load: losses 132.9 MWMagnitudes
Each point is one bus, in the case's bus order. The case's limits are 0.94 and 1.06 per unit. Holding the generators to their reactive limits turns the ones that exceed them into fixed-Q injections; the buses around them move.
held = vp.power.runpf("case118", enforce_q_lims=True)
moved = np.argsort(-abs(held.vm - nr.vm))[:3]
at_limit = np.isclose(held.qg, held.gen[:, 3]) | np.isclose(held.qg, held.gen[:, 4])
print("generators held at a reactive limit:", int(at_limit.sum()))
print("with Q limits: %d iterations; largest change %.4f per unit at buses %s" %
(held.iterations, abs(held.vm - nr.vm).max(), ", ".join(str(int(nr.bus[i, 0])) for i in moved)))
bus = nr.bus[:, 0]
fig = figure("Bus voltage magnitudes, case118", "bus", "Vm (per unit)", window=(0.0, 119.0, 0.93, 1.07))
fig.scatter(bus, nr.vm, "Newton-Raphson")
fig.scatter(bus, held.vm, "with Q limits")
fig.hline("Vmin", 0.94)
fig.hline("Vmax", 1.06)generators held at a reactive limit: 6
with Q limits: 6 iterations; largest change 0.0093 per unit at buses 103, 92, 102Angles, AC against DC
The DC model gets the angles from one linear solve, with the reference bus (bus 69) held at its angle. Here its angles sit a few degrees off the AC ones across most of the network, and its branch flows differ by tens of MW on the most loaded branches.
dc = vp.power.runpf("case118", method="dc")
err = dc.va - nr.va
print("DC angle error: largest %.2f degrees, mean |error| %.2f degrees" % (abs(err).max(), abs(err).mean()))
print("DC branch flow error: largest %.1f MW" % abs(dc.pf - nr.pf).max())
fig = figure("Bus voltage angles, case118", "bus", "Va (degrees)")
fig.plot(bus, nr.va, "Newton-Raphson")
fig.plot(bus, dc.va, "DC model")DC angle error: largest 5.31 degrees, mean |error| 2.32 degrees
DC branch flow error: largest 59.6 MWCredits